百米管道保温体积估量表
2008年06月29 00:00:00 来源:中国制冷空调技术网
百米管道保温体积估量表(m3/100m)
| 公称 直径 |
15 | 20 | 25 | 32 | 40 | 50 | 65 | 80 | 100 | 125 | |
| 管道 外径 |
18 | 25 | 32 | 38 | 45 | 57 | 76 | 89 | 108 | 133 | |
| 保 温 层 厚度 |
10 | 0.1 | 0.1 | 0.1 | 0.2 | 0.2 | 0.2 | 0.3 | 0.3 | 0.4 | 0.4 |
| 15 | 0.2 | 0.2 | 0.2 | 0.2 | 0.3 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | |
| 20 | 0.3 | 0.3 | 0.3 | 0.4 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 1.0 | |
| 25 | 0.4 | 0.4 | 0.4 | 0.5 | 0.5 | 0.6 | 0.8 | 0.9 | 1.0 | 1.2 | |
| 30 | 0.5 | 0.5 | 0.6 | 0.6 | 0.7 | 0.8 | 1.0 | 1.1 | 1.3 | 1.5 | |
| 35 | 0.6 | 0.7 | 0.7 | 0.8 | 0.9 | 1.0 | 1.2 | 1.4 | 1.6 | 1.8 | |
| 40 | 0.8 | 0.9 | 0.9 | 1.0 | 1.1 | 1.2 | 1.4 | 1.6 | 1.9 | 2.2 | |
| 45 | 0.9 | 1.0 | 1.1 | 1.2 | 1.3 | 1.4 | 1.7 | 1.9 | 2.2 | 2.5 | |
| 50 | 1.1 | 1.2 | 1.3 | 1.4 | 1.5 | 1.7 | 1.9 | 2.2 | 2.5 | 2.9 | |
| 55 | 1.3 | 1.4 | 1.5 | 1.6 | 1.7 | 1.9 | 2.2 | 2.5 | 2.8 | 3.2 | |
| 60 | 1.5 | 1.7 | 1.7 | 1.8 | 2.0 | 2.2 | 2.5 | 2.8 | 3.2 | 3.6 | |
| 65 | 1.8 | 1.9 | 2.0 | 2.1 | 2.2 | 2.5 | 2.8 | 3.1 | 3.5 | 4.0 | |
| 70 | 2.0 | 2.2 | 2.2 | 2.4 | 2.5 | 2.8 | 3.1 | 3.5 | 3.9 | 4.5 | |
| 80 | 2.6 | 2.7 | 2.8 | 3.0 | 3.1 | 3.4 | 3.8 | 4.2 | 4.7 | 5.4 | |
| 90 | 3.2 | 3.3 | 3.4 | 3.6 | 3.8 | 4.2 | 4.6 | 5.1 | 5.6 | 6.3 | |
| 100 | 3.8 | 4.0 | 4.1 | 4.3 | 4.6 | 4.9 | 5.4 | 5.9 | 6.5 | 7.3 | |
| 120 | 5.4 | 5.6 | 5.7 | 6.0 | 6.2 | 6.7 | 7.3 | 7.9 | 8.6 | 9.5 | |
| 140 | 7.1 | 7.4 | 7.6 | 7.8 | 8.1 | 8.7 | 9.4 | 10.1 | 10.9 | 12.0 | |
| 160 | 9.1 | 9.4 | 9.7 | 10.0 | 10.3 | 10.9 | 11.7 | 12.5 | 13.5 | 14.7 | |
| 180 | 11.4 | 11.8 | 12.0 | 12.3 | 12.7 | 13.4 | 14.3 | 15.2 | 16.3 | 17.7 | |
| 200 | 13.9 | 14.3 | 14.6 | 15.0 | 15.4 | 16.1 | 17.2 | 18.2 | 19.4 | 20.9 | |
| 220 | 16.7 | 17.1 | 17.4 | 17.8 | 18.3 | 19.1 | 20.3 | 21.4 | 22.7 | 24.4 | |
| 公称直径 | 150 | 200 | 250 | 300 | 350 | 400 | 450 | 500 | 600 | 700 | |
| 管道外径 | 159 | 219 | 273 | 325 | 377 | 426 | 478 | 530 | 630 | 720 | |
| 保 温 层 厚 度 |
0.5 | 0.7 | 0.9 | 1.1 | 1.2 | 1.4 | 1.5 | 1.7 | 2.0 | 2.3 | |
| 0.8 | 1.1 | 1.4 | 1.6 | 1.8 | 2.1 | 2.3 | 2.6 | 3.0 | 3.5 | ||
| 1.1 | 1.5 | 1.8 | 2.2 | 2.5 | 2.8 | 3.1 | 3.4 | 4.1 | 4.6 | ||
| 1.4 | 1.9 | 2.3 | 2.7 | 3.2 | 3.5 | 4.0 | 4.4 | 5.1 | 5.9 | ||
| 1.8 | 2.3 | 2.9 | 3.3 | 3.8 | 4.3 | 4.8 | 5.3 | 6.2 | 7.1 | ||
| 2.1 | 2.8 | 3.4 | 4.0 | 4.5 | 5.1 | 5.6 | 6.2 | 7.3 | 8.3 | ||
| 2.5 | 3.3 | 3.9 | 4.6 | 5.2 | 5.9 | 6.5 | 7.2 | 8.4 | 9.6 | ||
| 2.9 | 3.7 | 4.5 | 5.2 | 6.0 | 6.7 | 7.4 | 8.1 | 9.5 | 10.8 | ||
| 3.3 | 4.2 | 5.1 | 5.9 | 6.7 | 7.5 | 8.3 | 9.1 | 10.7 | 12.1 | ||
| 3.7 | 4.7 | 5.7 | 6.6 | 7.5 | 8.3 | 9.2 | 10.1 | 11.8 | 13.4 | ||
| 4.1 | 5.3 | 6.3 | 7.3 | 8.2 | 9.2 | 10.1 | 11.1 | 13.0 | 14.7 | ||
| 4.6 | 5.8 | 6.9 | 8.0 | 9.0 | 10.0 | 11.1 | 12.1 | 14.2 | 16.0 | ||
| 5.0 | 6.4 | 7.5 | 8.7 | 9.8 | 10.9 | 12.1 | 13.2 | 15.4 | 17.4 | ||
| 6.0 | 7.5 | 8.9 | 10.2 | 11.5 | 12.7 | 14.0 | 15.3 | 17.8 | 20.1 | ||
| 7.0 | 8.7 | 10.3 | 11.7 | 13.2 | 14.6 | 16.1 | 17.5 | 20.4 | 22.9 | ||
| 8.1 | 10.0 | 11.7 | 13.4 | 15.0 | 16.5 | 18.2 | 19.8 | 22.9 | 25.8 | ||
| 10.5 | 12.8 | 14.8 | 16.8 | 18.7 | 20.6 | 22.5 | 24.5 | 28.3 | 31.7 | ||
| 13.2 | 15.8 | 18.2 | 20.5 | 22.7 | 24.9 | 27.2 | 29.4 | 33.9 | 37.8 | ||
| 16.0 | 19.1 | 21.8 | 24.4 | 27.0 | 29.5 | 32.1 | 34.6 | 39.7 | 44.2 | ||
| 19.2 | 22.6 | 25.6 | 28.6 | 31.5 | 34.3 | 37.2 | 40.1 | 45.8 | 50.9 | ||
| 22.6 | 26.3 | 29.7 | 33.0 | 36.3 | 39.3 | 42.6 | 45.8 | 52.2 | 57.8 | ||
| 26.2 | 30.3 | 34.1 | 37.7 | 41.3 | 44.6 | 48.2 | 51.8 | 58.7 | 65.0 |