间歇运行对翅片管式蒸发器长效特性的影响

2012年02月28 00:00:00 来源:中国空调制冷网

【中文摘要】 研究了翅片管式蒸发器在空调器长期运行中,由于间歇运行对于其换热和空气侧压降的影响。实验对象为一个铝翅片铜管换热器和一个铜管铜翅片换热器。实验表明,经过多次间歇运行后,蒸发器的换热系数明显下降,空气侧压降有所增大,铜翅片铜管换热器的长效换热特性强于铝翅片铜管换热器,两者的长效压降特性相当。

【英文摘要】 The effects of long-term intermittent operation on the air-side heat transfer and pressure drop performance of finned coil type evaporators of air conditioners are investigated by experiments on an aluminum-fin evaporator and a copper-fin evaporator. The test results indicate that the air-side heat transfer coefficient decreases and the pressure drop increases after a long-term intermittent operation,and the influence of long-term intermittent operations on heat transfer coefficient of the aluminum-fin evaporator is larger than that of the copper-fin evaporator while the influence of the long term intermittent operation on the pressure drop of both type evaporators are identical.

【中文关键词】 蒸发器; 换热; 压降; 间歇运行

【英文关键词】 evaporator; heat transfer; pressure drop; intermittent operation